STATION 2 · Q6
Station 2, Task 6: gate control circuit
This page covers the sequence of operation, the time limit and the materials of Station 2 (Task 6: gate control circuit) of the Taiwan Level B interior wiring technician practical exam. On this site you can practice wiring, crimping and a test run in the browser following the circuit diagram and the arrangement drawing, with automatic grading against the assessment sheet.

Sequence of operation (動作說明)
A single-phase capacitor-start motor opens and closes the gate: MCF opens it, MCR closes it.
- 1Someone passes the through-beam photoelectric switch PH1 outside the gate from outside to inside (beam blocked)
MCF opens the gate, and the time-delay relays TR1 and TR3 time out in turn and reset.
- 2The gate is fully open and presses the limit switch LS1
Opening stops and TR5 starts timing.
- 3TR5 times out
MCR closes the gate automatically until it presses LS2.
- 4Someone passes PH2 inside the gate from inside to outside
The gate opens and closes the same way (TR2, TR4).
- 5Someone passes while the gate is closing
It stops closing and opens again.
Workmanship rules
There is also an emergency stop button EMS and TH-RY overload protection; the photoelectric switches are supplied from before EMS. The supply is single-phase two-wire 220V and the main circuit is pre-wired at the test site; candidates wire the control circuit (1.25 mm² yellow) and the ground wires (2 mm² green).
Time limit and materials
Time limit: 90 min
Wire and crimp terminals issued to candidates
From the official list of materials issued to candidates; the test site gives more when you run out.
| Name | Specification | Quantity |
|---|---|---|
| PVC-insulated wire | 600V, 1.25mm², yellow | 1 roll |
| PVC-insulated wire | 600V, 2mm², green | 1 m |
| Crimp terminal | 1.25mm²-4, "Y" | 50 pcs |
| Crimp terminal | 2mm²-5, "O" | 6 pcs |
Devices installed at the test site
| Name | Specification | Quantity |
|---|---|---|
| Mounting board | 900×600×1.6tmm, painted steel | 1 pcs |
| Molded-case circuit breaker | 2P, 220V, 50AF, 15AT, IC5kA | 1 pcs |
| D-type fuse | 500V, 2A, with fuse base | 2 pcs |
| Contactor | AC 1φ 220V 2.2kW(3HP), coil 220V, 3P, auxiliary contacts 2a2b, 2 units, reversing, mechanical interlock | 1 set |
| Photoelectric switch | infrared, AC 220V, contact 1c, through-beam, with emitter and receiver | 2 set |
| Limit switch | 1a1b, 10A, 250V, plunger type | 2 pcs |
| Emergency stop pushbutton (red) | 30mmφ, 600V, 1a1b, push-lock, red, maintained | 1 pcs |
| Thermal overload relay | 6.8A, adjustable, 2-heater | 1 pcs |
| Auxiliary relay | AC 220V, 5A, 2C, with socket | 2 pcs |
| Auxiliary relay | AC 220V, 5A, 3c, with socket | 2 pcs |
| Time-delay relay | AC 220V, 0-10sec, time-delay contact 1c, instantaneous contact 1a, ON Delay, with socket | 5 pcs |
| Indicator light (red) | AC 220V/15V, 18V bulb, 30mmφ | 2 pcs |
| Indicator light (yellow) | AC 220V/15V, 18V bulb, 30mmφ | 2 pcs |
| Terminal block | 3P, 600V, 20A | 1 pcs |
| Terminal block | 4P, 600V, 20A | 1 pcs |
| Terminal block | 16P, 600V, 20A | 2 pcs |
| Terminal block | 10P, 600V, 20A | 1 pcs |
| Main ground bar (接地極端子板) | copper, 4P | 1 pcs |
| Equipment ground bar (接地線端子板) | copper, 5P | 1 pcs |
| Single-phase induction motor | 1φ 110V/220V 3/4HP, with electromagnetic brake (a standard motor may be used at the test site) | 1 unit |
Practicing this task here
New devices in Task 6: through-beam photoelectric switches PH1 (outside the gate) and PH2 (inside) (emitter+receiver, AC 220V, 1c output, c–a closes when the beam is blocked; mounted on the mounting board outside the box, leads pre-wired to TB5); TR1–TR5 are on-delay relays (②⑦ supply, ⑧ common, ⑥ time-delay a, ⑤ time-delay b; TR1 and TR2 also have instantaneous contacts ①c ③a ④b, while on TR3–TR5 ①c ③a ④b is a second time-delay contact); X3 and X4 are 11-pin 3c auxiliary relays (②⑩ coil, ①c ④a ⑤b, ③c ⑥a ⑦b, ⑪c ⑨a ⑧b); LS1 and LS2 are limit switches on the back of the enclosure door (pressed by hand); the motor is a single-phase capacitor-start motor (MCF and MCR switch the auxiliary winding → open, close the gate). During the test run, click a photoelectric switch beam to block it (someone passing); the limit switches can be held down or pressed once.
Open the simulator, pick this task and click terminals to wire it (normal mode routes wires automatically; in realistic mode you strip the wires, crimp the terminals and pull the wires into the wiring duct yourself). When you are done, switch to test run and operate it with power on, then submit for grading: the assessment sheet lists the demerits and where they are.
Full instructions: How to use
Practice this task →